Power supply:
20-30 VAC/VDC, 10 VA @ 24
VAC; Low temp option: 20-30
VAC/VDC, 35 VA @ 24 VAC
|
Output:
KCOP-R Two SPDT relay contacts, 240 VAC, 2A resistive.
KCOP-A 4-20 mA into 500Ω maximum
|
Sensor life:
Approximately 5 years
|
Detection range:
0-200 ppm
|
Accuracy:
±2.5% full scale
|
Sensing technology:
Electrochemical
|
Alarm setpoints:
Warning/alarm; 10/20 ppm, 25/50 ppm
or 50/100 ppm, jumper selectable, (KCOP-R only)
|
LED indication Status:
Green; Power on,
microprocessor operating properly, Amber;
|
Warning stage delay:
30 seconds (KCOP-R only)
|
Response time:
30 seconds to warning,
13 minutes to alarm (KCOP-R only)
|