HOME > KMC HVAC Parts > Electric Actuators > TSP-5000 Series
Previous Page
These combination air flow transducers and actuator
units are designed primarily for variable air volume
terminal units controlled via Direct Digital Control
(DDC) systems such as KMC's Digital System. They can
be used in slave or dual duct tracking applications.
Air flow is sensed by utilizing a single or multi-point
differential (velocity) pressure measuring station
or pitot tube. Air flow sensing is accomplished utilizing
twin platinum resistance temperature detectors. Velocity
measurement is maintained at 3% accuracy over the
range of 0 to 3,300 feet per minute (FPM).
Each unit mounts directly to a 1/2" diameter
or 3/8" square damper shaft, or a 3/8" diameter
shaft (HFO-0011 shaft adaptor required). Damper control
is provided by an 18o/minute or 60o/minute
actuator. The actuator is controlled by an SPDT 'floating'
input (on the TSP-5003/5023) or 2 to 10 VDC proportional
input (on the TSP-5002/5022). A minimum of 50 in-lbs.
torque is provided. Both minimum and maximum stops
are standard to limit the rotation. A gear disengagement
feature allows positioning the damper and/or gear-train
without energizing the actuator.
A 10,000 ohm, 1/3 watt feedback potentiometer is standard
on the TSP-5003/5023 (only).
A single or double auxiliary switch may be field installed.
Accessories are available:
-
CME-1002 Single auxiliary switch
-
CME-1004 Double auxiliary switch
-
HMO-1003 Replacement non-rotation bracket (one included)
-
HFO-0011 3/8" shaft adaptor
-
HMO-4518 Connector for 1/2" flexible metal conduit
-
HMO-4520 Compression connector for plenum cable
-
HMO-4526 Female connector for 1/2" conduit
|